Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Minimum 1 hr Critical Load (kW) Average 1 hr Critical Load (kW) Average Daytime 1 hr Critical Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 789 1,493 1,913 2,713 60 178 248 306 0 107 440 1,223 79 307 106 103 0 0 1,956 17 5,432 13 86 31,018 2,448,356 1,504,135 544,453
mg1 675 789 1,493 1,913 2,713 211 403 498 713 265 143 0 2,852 0 0 311 709 0 0 3,571 29 4,637 29 607 58,985 5,595,752 3,441,985 1,176,651
mg2 646 789 1,493 1,913 2,713 25 139 216 385 0 96 0 1,538 0 0 203 443 0 0 1,837 16 5,512 16 634 28,623 3,164,710 1,990,300 688,977
Summary None 789 1,493 1,913 2,713 296 720 962 1,404 265 346 440 5,613 79 307 620 1,255 0 0 7,364 21 15,581 19 86 118,626 11,208,818 6,936,420 2,410,081

Report Generated

2024-04-03 19:59:27.488914

User Warnings

Pre-existing battery battery_634_existing will not be utilized to support loads in microgrid mg0.
Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Cost Estimate ($)
mg0 mg0 Microgrid Design 100,000
mg0 mg0 Microgrid Controls 100,000
mg0 632633 SCADA disconnect switch 50,000
mg0 634a_data_center AMI disconnect meter 300
mg0 634b_radar AMI disconnect meter 300
mg0 634c_atc_tower AMI disconnect meter 300
mg1 mg1 Microgrid Design 100,000
mg1 mg1 Microgrid Controls 100,000
mg1 671692 SCADA disconnect switch 50,000
mg1 675a_hospital 3-phase relay 20,000
mg1 675b_residential1 3-phase relay 20,000
mg1 675c_residential1 3-phase relay 20,000
mg1 692_warehouse2 3-phase relay 20,000
mg2 mg2 Microgrid Design 100,000
mg2 mg2 Microgrid Controls 100,000
mg2 632645 SCADA disconnect switch 50,000
mg2 645_hangar AMI disconnect meter 300
mg2 646_office AMI disconnect meter 300

Description